General specifications |
Signal type | Analog input |
Supply |
Connection | Power Rail or terminals 7+, 8- |
Rated voltage | 20 ... 35 V DC |
Ripple | within the supply tolerance |
Power dissipation | ≤ 1.6 W |
Power consumption | ≤ 2 W |
Interface |
Protocol | Honeywell DE |
Input |
Connection side | field side |
Connection | terminals 1+, 3- |
Input signal | 4 ... 20 mA |
Available voltage | approx. 17 V at 4 ... 20 mA |
Output |
Connection side | control side |
Connection | terminals 9+, 10-, 11+ |
Output signal | 4 ... 20 mA , max. load 1000 Ω , for HART ≥ 230 Ω, Honeywell DE 230 ... 280 Ω (transmitter and communicator dependent) |
Ripple | ≤ 0.05 % of output signal range |
Transfer characteristics |
Deviation | ≤ 0.05 % of output signal range (current output), ≤ 10 µA at 20 °C (68 °F) |
| Influence of ambient temperature | ≤ 20 ppm/K |
Frequency range | field side into the control side: bandwidth with 1 mApp signal 0 ... 40 kHz (-1 dB); 0 ... 50 kHz (-6 dB) safe area to hazardous area: bandwidth with 250 mVpp signal 2 Hz ... 40 kHz (-1 dB); 1 Hz ... 50 kHz (-6 dB) |
Rise time | 10 µs |
Galvanic isolation |
Output/power supply | functional insulation, rated insulation voltage 50 V AC |
Indicators/settings |
Display elements | LED |
Labeling | space for labeling at the front |
Directive conformity |
Electromagnetic compatibility | |
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
Conformity |
Electromagnetic compatibility | NE 21:2006 |
Degree of protection | IEC 60529:2001 |
Ambient conditions |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Mechanical specifications |
Degree of protection | IP20 |
Connection | screw terminals |
Mass | approx. 150 g |
Dimensions | 20 x 115 x 115 mm (0.8 x 4.5 x 4.5 inch) , housing type B1 |
| Height | 115 mm |
| Width | 20 mm |
| Length | 115 mm |
Data for application in connection with hazardous areas |
EU-type examination certificate | BAS 01 ATEX 7369 |
| Marking | II (1)G [Ex ia Ga] IIC , II (1)D [Ex ia Da] IIIC , I (M1) [Ex ia Ma] I |
| Input | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I |
| Voltage | 25.2 V DC |
| Current | 93 mA |
| Power | 587 mW |
Supply | |
| Maximum safe voltage | 250 V (Attention! The rated voltage can be lower.) |
Certificate | BASEEFA 09 ATEX 0218X |
| Marking | II 3G Ex nA II T4 Gc [device in zone 2] |
Galvanic isolation | |
| Input/Output | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
| Input/power supply | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
Directive conformity | |
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 |
International approvals |
UL approval | |
| Control drawing | 116-0173 (cULus) |
IECEx approval | IECEx BAS 06.0088 IECEx BAS 09.0102X |
| Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I Ex nA II T4 Gc |
General information |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |