Serviceline Industrial Sensors
Serviceline Explosion Protection

구매 불가 제품

This product has been replaced.Go to replacement product KCD2-STC-1.2O
구매 불가 제품
구매 불가 제품

SMART Transmitter Power Supply KCD2-STC-1.2O

KCD2-STC-1.2O
  • 1-channel signal conditioner
  • 24 V DC supply (Power Rail)
  • Input for 2-wire SMART transmitters and current sources
  • Signal splitter (1 input and 2 outputs)
  • Dual output 0/4 mA ... 20 mA or 0/1 V ... 5 V
  • Terminal blocks with test sockets
  • Up to SIL 2 acc. to IEC 61508

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

PDF 파일로 된 데이타 시트 다운로드:


데이타 시트 발췌: 기술 사양  KCD2-STC-1.2O

제품 설명
Input 0/4 mA ... 20 mA
2 x Output 0/4 mA ... 20 mA
General specifications
Signal typeAnalog input
Supply
ConnectionPower Rail or terminals 9+, 10-
Rated voltage18 ... 30 V DC
Ripplewithin the supply tolerance
Power dissipationapprox. 1.4 W at 20 mA transfer current, 250 Ω in both outputs
Power consumption2 W
Input
Connectionterminals 1+, 2- (sink); 3+, 4- (source)
Input signal0/4 ... 20 mA
Open circuit voltage/short-circuit currentterminals 1+, 2-: 17 V/25 mA
Voltage dropterminals 3, 4: ≤ 6.1 V at 20 mA
Input resistanceterminals 1+, 2-: max. 500 Ω
(250 Ω load)
Available voltageterminals 1+, 2-: ≥ 16 V at 20 mA
Output
Connectionsource: terminals 5-, 6+; 7-, 8+
sink: terminals 5+, 6-, 7+, 8-
Loadchannel 1: 0 ... 500 Ω (20 mA)/< 1 MΩ (5 V)
channel 2: 0 ... 500 Ω (20 mA)/< 1 MΩ (5 V)
Output signal0/4 ... 20 mA or 0/1 ... 5 V
Ripplemax. 50 µA rms
Transfer characteristics
DeviationIout < 20 µA; Vout < 7.5 mV incl. calibration, linearity, hysteresis and fluctuation of supply voltage,
at 20 °C (68 °F), 0/4 ... 20 mA, 0/1 ... 5 V

Influence of ambient temperature0.25 µA/K
Frequency rangefield side into the control side: bandwidth with 0.5 Vpp signal 0 ... 7.5 kHz (-3 dB)
control side into the field side: bandwidth with 0.5 Vpp signal 0.3 ... 7.5 kHz (-3 dB)
Settling time200 µs
Rise time/fall time20 µs
Galvanic isolation
Output/power supplyfunctional insulation, rated insulation voltage 50 V AC
Output/Outputfunctional insulation, rated insulation voltage 50 V AC
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibilityNE 21:2006
Degree of protectionIEC 60529:2001
Protection against electrical shockUL 61010-1:2012
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Massapprox. 100 g
Dimensions12.5 x 114 x 122 mm (0.5 x 4.5 x 4.8 inch) , housing type A2
Height114 mm
Width12.5 mm
Length122 mm
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
General information
NoteBoth output loads must be connected to ensure complete and correct operation within the technical specification.
Supplementary informationStatement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027210119
ECLASS 12.027210119
ECLASS 11.027210119
ECLASS 10.0.127210119
ECLASS 9.027210119
ECLASS 8.027210119
ECLASS 5.127210119
ETIM 9.0EC001485
ETIM 8.0EC001485
ETIM 7.0EC001485
ETIM 6.0EC001485
ETIM 5.0EC001485
UNSPSC 12.132101514

Details: KCD2-STC-1.2O

Product Documentation: KCD2-STC-1.2O

Language Selection:
Safety and Security Documentation언어파일 타입파일 크기
Instruction manualENGPDF41 KB
Manuals
ManualENGPDF3685 KB

Design / Simulation: KCD2-STC-1.2O

Language Selection:
CAD언어파일 타입파일 크기
CAD 2-D / CAD 2-DALLZIP458 KB
CAD 3-D / CAD 3-DALLSTP179 KB
CAD Portal / CAD PortalALLLINK---

Approvals: KCD2-STC-1.2O

Language Selection:
Declaration of Conformity인증서 번호언어파일 타입파일 크기
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-2340AALLPDF71 KB
Safety Products Selector

Choose from various selection criteria like safety integrity level, performance level, device function, and signal type and find the SIL/PL assessed device that you are looking for.